Микропереключатель NO против NC: в чем разница?

Normally open and normally closed describe the state of the contacts before anything touches the switch — not the state of the machine, and not the state of the power supply. Getting this backwards is one of the most common wiring errors, and in a safety circuit it is the difference between a guard that fails safe and a guard that fails dangerous.

Updated Ноябрь 2026 Dongnan Electronics Co., Ltd. engineering team

What normally open and normally closed mean

A micro switch has a moving contact and two fixed contacts. In the unactuated state — nothing pressing the plunger — the moving contact rests against one of them:

  • Normally open (NO): the circuit through that contact is broken at rest. Pressing the actuator closes it.
  • Normally closed (NC): the circuit is complete at rest. Pressing the actuator breaks it.

“Normal” here means mechanical rest, not electrical off. A switch mounted in a closed door is being held actuated all day, so its rest state is the door-open state. Always ask “rest with respect to what?” before designing around the term.

The truth table

State COM–NO COM–NC
Actuator at rest Open Closed
Actuator pressed Closed Open
Actuator released Open Closed
Broken wire or failed spring Open Open

The last row is the one that matters for safety: both contacts end up open when the switch or its wiring fails. Only the NC contact fails in the safe direction for a circuit that is supposed to be closed.

Why safety circuits use NC

Take a machine guard. The circuit that powers the motor runs through the switch. If the switch uses NO, the motor runs only while the guard is closed and the switch is pressed — sounds correct, but a severed wire or a broken spring also makes the contact open, which stops the motor. Actually that is safe. Now invert the logic: an emergency stop button wired NO would only work while the circuit is intact; a broken wire means pressing it does nothing.

The rule is simpler than the reasoning: the safe state should be the unpowered, de-energised, open-circuit state, and the switch should have to be actively held in the other state. That is why emergency stops, door interlocks and guard switches use NC contacts: loss of power, a broken wire or a worn switch all produce a stop, which is the safe outcome. NO contacts are for signals and start commands, where a failure to detect is annoying rather than dangerous.

Typical circuits for each

Приложение Контакт Reason
Door interlock (power cut when open) NC Broken wire stops the machine
Emergency stop NC Fail-safe by design
Presence / position detection NO Signal only; a false negative stops nothing
Start button NO Momentary command
Limit switch on a moving axis NC (typically) Loss of signal stops motion
Coin or card detection NO Event counting

Most micro switches are SPDT, which gives you both contacts in one part. Use NC for the safety path and NO for the status signal — that is why SPDT is the default configuration rather than SPST.

How to tell which one you have

With a multimeter in continuity mode and the switch disconnected:

  1. At rest, the beeping pair is COM and NC.
  2. Press the actuator; the beeping pair becomes COM and NO.
  3. The terminal in both pairs is COM.

If the switch is already wired into a machine, disconnect power first and test at the terminals. A reading that changes when you press the actuator confirms the contact is working; a reading that stays closed confirms you are on NC.

How to choose

  • Ask what happens when the switch fails. If the answer must be “the machine stops”, use NC.
  • Ask what happens when a wire breaks. Same rule: NC if the failure must be safe.
  • Use SPDT when you need both a safety contact and a status signal, which is most of the time.
  • Do not mix logic. A controller that reads NC as “door closed” will invert the meaning of every downstream diagnostic; document the convention.

For terminal identification and wiring examples, see micro switch wiring diagrams. For part selection, see the Руководство по выбору микропереключателей..

Frequently asked questions

Что означает "обычно открыто" на микровыключателе?

При отсутствии движения актуатора цепь между общим и NO-контактами разрывается, а при нажатии на актуатор она замыкается. Этот контакт используется для команд запуска и сигналов обнаружения.

Что означает "обычно закрыто"?

Цепь между общим и НО-контактами замкнута в состоянии покоя и размыкается при нажатии на привод. Этот контакт используется в случаях, когда поврежденный провод или неисправный выключатель должны остановить работу машины.

Can I use NO instead of NC for a door switch?

Only if the door switch is purely a status signal. For a safety interlock that must cut power, NC is required, because an NO contact cannot distinguish “door closed” from “wire broken”.

How can I tell NO from NC without a meter?

Look for the moulded markings COM, NO and NC on the housing. If they are worn off, the terminal layout is not reliable evidence — use a multimeter.

Is SPDT normally open or normally closed?

Both. An SPDT switch has one common terminal and two fixed contacts, so it provides an NO and an NC contact in the same part.