A micro switch is one of the simplest components to wire, and one of the easiest to wire wrong. The three terminals look interchangeable, the contacts are hidden inside the housing, and the difference between the normally open and normally closed pair is invisible until the machine behaves backwards. This guide covers the terminals, how to identify them with a multimeter, the common circuits, and the mistakes that cause field failures.
On this page
The three terminals and what they do
A standard SPDT micro switch has three terminals:
- COM — common. Connected to the moving contact. Always one side of your circuit.
- NO — normally open. Disconnected from COM at rest; connects when the actuator is pressed.
- NC — normally closed. Connected to COM at rest; opens when the actuator is pressed.
“Normally” refers to the unactuated state, not to the powered state. A switch mounted in a door latch is actuated while the door is closed, so its “normal” state is the door-open state.
| Terminal pair | At rest | Pressed | Typical use |
|---|---|---|---|
| COM–NO | Open circuit | Closed | Start, detect, signal |
| COM–NC | Closed circuit | Open | Interlock, stop, fail-safe |
| NO–NC | Open | Open | Never use; no circuit in either state |
Identifying COM, NO and NC without a datasheet
If the markings are worn off, a multimeter in continuity mode identifies the terminals in three steps:
- With the actuator at rest, find the pair that beeps. Those two are COM and NC.
- Press and hold the actuator. The pair that now beeps is COM and NO.
- The terminal common to both pairs is COM.
If you cannot press the actuator because it is inside an assembly, look at the moulded markings: COM is usually in the middle, NO and NC on the outside. Never assume — manufacturers vary the layout between series.
Two-wire and three-wire hookups
Two-wire means you use only two of the three terminals: COM and either NO or NC. The switch behaves as a simple on/off contact. Choose NO when the circuit should close on actuation, NC when it should open.
Three-wire is not electrically different — it simply means all three terminals are used, typically to feed a controller input and a separate indicator or relay. Some three-wire micro switches exist in a moulded housing with a pre-terminated cable; inside, they are still SPDT contacts.
If you are replacing a three-wire switch, photograph the terminals before removing it. The wire colours are not standardised across manufacturers; the terminal positions are.
Six common wiring diagrams
| Схема | Connection | Notes |
|---|---|---|
| Load on when pressed | Supply → COM, NO → load → neutral | Simplest momentary action |
| Load off when pressed | Supply → COM, NC → load → neutral | Fail-safe door interlock |
| Relay coil drive | Supply → COM, NO → relay coil → neutral | Switch carries coil current only; coil is fused separately |
| PLC digital input (sinking) | Input → NO, COM → 0 V | Use gold contacts for dry-circuit inputs |
| PLC digital input (sourcing) | +24 V → COM, NO → input | Check the PLC input type before wiring |
| Two-speed / changeover | COM common, NO and NC to two different loads | Only one load is energised at a time |
Switching a load directly or through a relay
A micro switch rated 10 A at 250 VAC can switch a small motor directly, but the inrush current of a motor is five to eight times its running current. If the switch is not rated for that inrush, the contacts weld. Two rules keep designs safe:
- Below roughly 2 A resistive, direct switching is fine for any decent micro switch.
- For motors, lamps, solenoids and anything with a large inrush, switch a relay or contactor coil instead and let the micro switch carry only the coil current.
For DC loads above about 24 V, check the DC rating. A switch rated 10 A at 250 VAC may be rated well under 1 A at 30 VDC, because a DC arc does not self-extinguish at the zero crossing.
Wire gauge, connectors and strain relief
Micro switch terminals are small, and the wire is usually the weakest part of the assembly.
- Gauge. 0.5 mm² (about 20 AWG) suits most control wiring; 0.75–1.0 mm² for loads above 5 A.
- Terminals. 2.8 × 0.5 mm and 4.8 × 0.5 mm spade terminals are standard; PCB pins suit automated assembly; screw terminals suit field wiring.
- Strain relief. Clamp the cable, not the terminal. A wire that tugs on a spade terminal eventually loosens and arcs.
- Sealing. If the switch is IP67 but the terminals are exposed, the assembly is not IP67 — water tracks along the strands into the switch.
Wiring mistakes that fail in the field
- Using NO where safety requires NC. A broken wire on an NO interlock looks identical to a closed door. Safety circuits use NC so that a failure opens the circuit.
- Switching the neutral instead of the live conductor. The switch appears to work but leaves the load live when off.
- Over-tightening the mounting screws. It distorts the housing and changes the contact gap, which changes the trip point and can weld the contacts.
- Ignoring the inrush current. The most common cause of welded contacts on appliance switches.
- No over-travel. A mechanism that presses the actuator exactly to the trip point will fail as soon as tolerances stack up.
If you are unsure which contact to use, see NO vs NC micro switch. For part selection, see the Руководство по выбору микропереключателей..
Frequently asked questions
Как подключить микровыключатель с двумя проводами?
Подключите один провод к COM, а другой к NO, если цепь должна замыкаться при нажатии, или к NC, если она должна размыкаться при нажатии. Оставьте третий терминал неподключенным.
Что такое 3-проводной микровыключатель?
Electrically it is a standard SPDT switch with all three terminals used — common, normally open and normally closed. The third wire usually feeds a controller input or an indicator. There is no separate “3-wire” mechanism.
Which terminal is common on a micro switch?
Usually the middle terminal, and it is the one common to both the rest-state and pressed-state continuity pairs. Confirm with a multimeter rather than assuming, because layouts vary between series.
Can a micro switch switch AC and DC?
It can switch whichever it is rated for. AC and DC ratings are different and the DC rating is usually much lower, because DC arcs sustain themselves instead of extinguishing at a zero crossing.
How do I test a micro switch with a multimeter?
Set the meter to continuity. With the actuator at rest, the COM–NC pair should beep and COM–NO should not. Press the actuator and the readings should reverse. If neither pair changes, the switch is faulty.